    How much fall a horizontal drain needs so it self-cleans, and an honest answer on the maximum that everyone argues about.

    Minimum slope, IPC Table 704.1

    2-1/2 in and smaller 1/4 in per ft (1:48)
    3 in to 6 in 1/8 in per ft (1:96)
    8 in and larger 1/16 in per ft (1:192)

    Cleanouts

    Horizontal drain inside the building At intervals not exceeding 100 ft
    Building sewer smaller than 8 in At intervals not exceeding 100 ft
    Building sewer 8 in and larger Manholes, within 200 ft of the junction then every 400 ft
    At direction changes Required at each change greater than 45 degrees
    Building drain vs building sewer Same slope table. The distinction is location and pipe material, not fall.

    Can a drain be TOO steep?

    • There is no numeric maximum slope in the IPC.
    • The workshop claim is that liquid outruns solids on a steep run and leaves them behind. It is widely repeated and genuinely disputed, and no code section sets a figure.
    • So: hit the minimum, keep it consistent, and do not let anyone tell you a steep run fails inspection on a number. Ask them which section.
    These are model-code figures from the IPC. Plumbing code adoption is state and often local, a good number of jurisdictions use the UPC instead, and amendments to slope and cleanout tables are common. Confirm against the plumbing code your jurisdiction has actually adopted before you set a fall.