Fire Extinguishers: Class, Placement, Paperwork

Which extinguisher fights which fire, what OSHA actually requires on a jobsite, and the records an inspector asks for.
The classes
| A | Wood, paper, cloth, most plastics |
| B | Flammable liquids and gases: gasoline, oil, paint, propane |
| C | Energized electrical equipment. The agent must be non-conductive. |
| D | Combustible metals: magnesium, titanium, sodium |
| K | Cooking oils and animal fats. Wet chemical. |
| Getting it wrong | Water or foam on a class B fire spreads it. On energized equipment it is an electrocution risk. |
What OSHA requires on a jobsite (29 CFR 1926.150)
| Coverage | At least one extinguisher rated 2A per 3,000 sq ft of protected building area, or major fraction of it |
| Travel distance | No more than 100 ft from any point to the nearest extinguisher |
| Multistory | One per floor, and one adjacent to the stairway |
| Flammables | A 10B unit within 50 ft of more than 5 gallons of flammable liquid, or 5 lb of flammable gas, in use |
| Prohibited | Carbon tetrachloride extinguishers |
NFPA 10, which is stricter
| Class A travel distance | 75 ft |
| Class B travel distance | 30 to 50 ft by hazard level |
| Class K travel distance | 30 ft |
| Mounting height | Top no more than 5 ft above the floor. Units OVER 40 LB mount lower, top no more than 3-1/2 ft. That threshold is WEIGHT, not accessibility. |
| Floor clearance | At least 4 in from the bottom to the floor |
Inspection and records
| Monthly | Visual check: condition, gauge, tamper seal, still accessible and unobstructed |
| Annual | Maintenance by a qualified person, with the date recorded on the tag |
| 6 years | Internal maintenance on stored-pressure units |
| 12 years | Hydrostatic test on dry chemical units |
Sources: osha.gov · nfpa.org