Wire Colors: What the NEC Requires vs What Is Just Habit

Neutral and ground colors are code. Hot colors are not, and most people think they are. Here is the line between them.
REQUIRED by code
| Grounded (neutral), 6 AWG and smaller | Continuous white or gray, or three continuous white/gray stripes. NEC 200.6(A) |
| Grounded (neutral), larger than 6 AWG | White/gray finish, three stripes, or distinctive white/gray marking at terminations. NEC 200.6(B) |
| White and gray are reserved | They may only identify the grounded conductor. NEC 200.7 |
| Equipment ground, 6 AWG and smaller | Green, or green with yellow stripes, for its entire length. NEC 250.119 |
| Equipment ground, larger than 6 AWG | May be re-identified green at every accessible point instead. |
NOT required, and this is the useful part
- There is NO NEC rule setting the color of an ungrounded (hot) conductor. Black, red and blue on 120/208, and brown, orange and yellow on 277/480, are trade convention. Widespread, sensible, and not a code requirement.
- What IS required: where a building has more than one voltage system, ungrounded conductors must be identified by system, the method must be used consistently, and it must be POSTED at each panelboard. NEC 210.5(C). The code cares that it is documented and consistent, not which color you picked.
- So a panel with unconventional hot colors and a posted legend can be compliant, while a conventional one with no legend is not.
The size threshold, stated plainly
- Sources word it as 'larger than 6 AWG' or '4 AWG and larger'. These are the SAME boundary. Standard AWG runs 6, 4, 3, 2, so there is no size in between.
Sources: nfpa.org
SiteKiln provides general guidance only. This is not legal, tax, financial or professional advice. Always verify information and seek professional advice if unsure. © SiteKiln 2026